ARME-AIS Series 36 kV Schneider Inside Metal Enclosed Switchgear are used in Schneider Brand of load breakers, SF6 load breakers and circuit breakers. All type tests were performed by KEMA-ICMET-LVT.
Rated Voltage | 36 kV |
Network Frequency Withstand Voltage 1min | 70 kV |
Clearance (Contacts) | 80 kV |
Lightning Impulse Withstand Voltage | 170 kV |
Clearance | 195 kV |
Rated Frequency | 50/60 Hz |
Rated Current | 630-1250 A |
Rated Short Circuit Withstand Current (1sec)(3sec) | 16-20-25 kA |
Rated Short Circuit Closing Current | 40 kA-tepe |
Mechanical Class | M2 |
Electrical Class | E2 |
Internal Arc Class | AFL |
Protection Class | IP3X |